• HV-LI/U-PROBES

Combi-PROBES

HV-LI/U-PROBES

Features
  • HV-LI-I/U – PROBES consist of a voltage- and a current-PROBE
Current measurement
  • The measuring shunt is placed in a grouted casing with cable lead-out for looping-in the PROBE into the measuring circuit
  • Protection of the measuring circuit has to be provided by the user
Voltage measurement
  • Measurement via a voltage divider to reduce the input voltage to an allowed voltage level for the modules
Construction
  • Grouted casing with integrated shunt (type PBV) and voltage divider
  • Memory device for PROBE-identification and calibration data (placed in connector)
  • I-PROBE, cable lead-out = L1 (1 m), (heat resistant and high flexible) with loose cable ends
  • U-PROBE, connection cable = L3 (0,5 m), (heat resistant and high flexible) with loose cable ends
  • Data cable = L2 (1/3/5m) with 8-pin Redel connector
circuit diagram
    • Current-PROBES (Type PBV)
      Resistor [mΩ]Measuring range [A]Resolution/Bit* [µA]Maximum permanent current ** [A]
      1000 -0,3…+0,72 0,25 0,72
      500 -0,6…+1,44 0,5 1,44
      100 -3…+7,2 2,5 6,5
      50 -6…+14,4 5 9,5
      25 -12…+28,8 10 12
      10 -30…+72 25 21
      5 -60…+144 50 25
      2 -150…+360 125 40
    • Voltage-PROBES (Type 1000 V)
      GainMeasuring range [V DC]Resolution/Bit [mV/Bit]
      100 0...+/- 37,5 1,25
      50 0...+/- 75 2,5
      24 0...+/- 150 5
      6 0...+/- 600 20
      1 0...+/- 1000 120

      size (l/w/h):50x40x16 mm
      * indicated for the lowest measuring range
      ** at room temperature (23°C)

    Order code

    <name> - <resistance value> - <L1> - <L2> - <L3>

    nameresistance valueL1L2L3
    HV-LI/U 1000/…/2 1 1/3/5 0,5